The Home page in PowerHub is where users select, view, and edit Tools and power POCs.

When the POCs of one or more tools are listed, attributes of both the tools and the POCs are displayed in the home page grid.

Grid Overview

The POC grid on the home page lists various attributes of POCs summarized as follows:

Attributes in GridTool/POCDescription
EntityToolName of tool
REFPOCTPOC reference
DescriptionPOCTPOC description
FAToolFunctional Area of the tool
CEIDToolModel type of the tool
BayToolBay the tool is located in
FACToolFacility the tool is located in
UTILPOCNormal (NPS), Emergency (EPS) or critical power supply (CPS)
TRNPOCPower train that the POC is connected to
TagPOCPower tag of the POC, used to restrict the POC to being connected to power panels with the same tag.
VPOCVoltage of the POC
FLAPOCFull Load Amperage of the POC as per the tool supplier, and written on the tool nameplate.
PHPOCPhase, number of hot wires used by the POC. Note that outside the USA, loads that require 2 hots are referred to as ‘two phase’ and this is how this field represents such loads.
kVA(CON)POCConnected kVA
PanelPOCName of Panel that POC is preassigned/connected to
CCTPOCCircuit number POC is preassigned/connected to
RoxtecPOCRoxtec that the POC passes through on way to panel
TripPOCBreaker Trip Name
kVA(DEM)POCDemand kVA allowing for measured demand data or default date for the assigned panel type
DFPOCDemand factor (measured or default)
SizePOCTrip Unit Size
SetPOCBreaker adjustment
LENPOCCable length (actual length, otherwise design length, otherwise auto calculated length) in metres (outside USA) or feet (USA).
CablePOCCable Size, mm2 (outside USA) or AWG (USA)
RCBO (Residual Current Breaker with Overcurrent)POCAlso known as GFCI (ground-fault circuit interrupter). Indicates that the circuit is protected by a RCBO/GFCI breaker.
Neutral PolePOCIndicates that the circuit requires a breaker with a neutral pole.
NotesPOCComments or other details relating to the POC